24hours
*6 Sales Manager
*20 Sales Assistant
* 5 Technical Engineer
*10 QC Inspector
*120 Professional Worker
Automation Relay,Circuit Breaker,Contactor,Isolation Switch,Light,Other Electrical Equipment,Pneumatic,Power Quality,Solar Energy Storage System,Surge Protection Device,Timer Switch,Topsales Products,Transfer Switch,Ungrouped
Indicator Type | Description |
Alarm | Slow flashing(1time per sec)when warn alarm occurs. Fast flashing(5 times per sec) when fault alarm occurs. |
Running | Flash when module countdown running(1time per sec) |
S1 Power Normal | It is light on when S1 is normal; flashing when S1 is abnormal (1time per sec); off when there is no S1 power. |
S1 Close Status | It is light on when S1 close input is activated. |
S2 Power Normal | It is light on when S2 is normal; flashing when S2 is abnormal(1time per sec); off when there is no S2 power. |
S2 Close Status | It is light on when S2 close input is activated. |
Manual Mode | It is light on when the module is in Manual mode. |
Auto Mode | It is light on when the module is in Auto mode. |
Generator Start | It is light on when the Start signal is be initiated. |
Function | ||||||||||||||
Type | DC Power | AC Power Supply | AC Current & Power | Sync Close | Input Ports (Fixed+Config.) | Output Ports (Fixed+Config.) | RS485 | |||||||
ATS700 | 2+4 | 2+6 | According to customer demand | |||||||||||
ATS700B | (LN90V~280V) | 2+4 | 2+6 | |||||||||||
ATS700I | 2+4 | 2+6 | ||||||||||||
ATS700BI | (LN90V~280V) | 2+4 | 2+6 |
ltems | Contents | ||||
Operating Voltage | 1.DC 8.0V~35.0V,continuous power supply. 2.AC90V~280V during AC power supply L1N1/L2N2(ATS700B/ATS700BI) | ||||
Power Consumption | <5W(Standby mode:≤2W) | ||||
AC Voltage Input | AC system | ATS700/ATS700I | ATS700B/ATS700BI | ||
3P4W(L-L) | (80~625)V | (80~480)V | |||
3P3W(L-L) | (80~625)V | (80~625)V | |||
1P2W(L-N) | (50~360)V | (50~280)V | |||
2P3W(A-B) | (80~625)V | (80~480)V | |||
Rated Frequency | 50/60Hz | ||||
Close Relay Output | 16A AC250V Volts free output | ||||
Auxiliary Relay Output | 16A/7A AC250V Volts free output | ||||
Digital lnput | GND (B-) connect is active. | ||||
Communication | RS485 isolated interface, MODBUS Protocol | ||||
Case Dimensions | 197mm*152mm*47mm | ||||
Panel Cutout | 186mm*141mm | ||||
Working Conditions | Temperature:(-25~+70)℃; Relative Humidity:(20~93)%RH | ||||
Storage Condition | Temperature:(-25~+70)℃ | ||||
Protection Level | IP55:when water proof gasket ring inserted between panel and housing. | ||||
Insulation Strength | Apply AC2.2kV voltage between high voltage terminal and low voltage terminal; The leakage current is not more than 3.5mA within 1min. | ||||
Weight | ATS700/ATS700I:0.7kg ATS700B/ATS700BI:0.8kg |