Mode | 160 | 250 | ||||||||||||
Number of poles | 2P | 2P | ||||||||||||
Rated operating voltage Ue AC (V) | 500 | 690 | 500 | 690 | ||||||||||
Rated operating voltage Ue DC(V) | 220 | 500 | 一 | 500 | ||||||||||
Rated operating current le(A) | 160 | 100 | 160 | 100 | 250 | 250 | 200 | |||||||
Fuse thermal overload current (A) | 160 | 160 | 160 | 160 | 250 | 250 | 250 | |||||||
Usage categories | DC22B | DC22B | AC22B | AC21B | DC22B | AC22B | AC21B | |||||||
Rated insulation voltage Ui (kV) | 1000 | 1000 | ||||||||||||
Rated impact withstand voltage Uimp (kV) | 8 | 8 | ||||||||||||
Rated limited short-circuit current (kA) | 50 | 50 | ||||||||||||
Rated frequency (Hz) | 50/60 | 50/60 | ||||||||||||
Single phase power loss (W) | 3.5 | 7.5 | ||||||||||||
Electrical life | 200 | 200 | ||||||||||||
Mechanical life | 1400 | 1400 | ||||||||||||
Front protection level according to IEC60529 | Open | IP20 | IP20 | |||||||||||
Closure | IP30 | IP30 |