Automation Relay,Circuit Breaker,Contactor,Isolation Switch,Light,Other Electrical Equipment,Pneumatic,Power Quality,Solar Energy Storage System,Surge Protection Device,Timer Switch,Topsales Products,Transfer Switch,Ungrouped
220V series | 380V series | 500V series | 690V series | ||||
Altitude | <2000m,above 2000m,derate according to GB/T3859.2 | ||||||
ambient temperature | -20~+50℃ | ||||||
Relative humidity | ≤90%,no condensation on the surface when the monthly minimum temperature is 25℃ | ||||||
pollution level | Level IIlbelow | ||||||
Operating Voltage | AC220V±20% | AC380V±20% | AC500V±20% | AC690V±20% | |||
working frequency | 50Hz±5% | ||||||
Compensation current | 25A | 25/50/75/100/150A | 100A | 100A | |||
Grid structure | L/N | 3P3W/3P4W | 3P3W/3P4W | 3P3W/3P4W | |||
Number of units connected in parallel | Ulimited | ||||||
Overallmachine efficiency | ≥97% | ||||||
Grid structure | 32kHz | 16kHz | 12.8kHz | 12.8kHz | |||
Compensation range | 2~50times,single compensation rate is adjustable | ||||||
Function selection | Reactive power | Reactive power,reactive power+asymmetry | |||||
Reactive power compensation rate | ≥95% | >92% | |||||
Neutral filtering capability | Neutral line filtering capability is 3 times that of phase filtering capability | ||||||
full response time | <10ms | <40ms | <40ms | <40ms | |||
noise | ≤60dB | ≤60dB | ≤65dB | ≤65dB | |||
control method | 2-way RS⁴85 interface (supports GPRS/WIFI) | ||||||
Protection | Overload, software/hardware overcurrent,grid overvoltage and undervoltage,power failure, overtemperature,frequency abnormality protection,etc | Overload,software/hardware overcurrent,grid overvoltage and undervoltage,grid voltage imbalance,power failure,overtemperature,frequency abnormality,short circuit protection,etc. | |||||
Installation method | Rack/wall-mounted | Rack | |||||
Incoming line | Back incoming(rack type)、 upper incoming(wall-mounted) | Back incoming line | |||||
Protection level | IP20 |