Automation Relay,Circuit Breaker,Contactor,Isolation Switch,Light,Other Electrical Equipment,Pneumatic,Power Quality,Solar Energy Storage System,Surge Protection Device,Timer Switch,Topsales Products,Transfer Switch,Ungrouped
Technical parameters | 3P3W | 3P4W | |
Function | Monitoring 3-phase voltage | ||
Monitoring terminials | L1-L2-L3 | L1-L2-L3-N | |
Supply terminals | L1-L2 L1-L2 | ||
Voltage range | 380-400-415-440-480 (P-P) | 220-230-240-254-277 (P-N) | |
Rated supply frequency | 45Hz-65Hz | ||
Measuring range | 260V-600V | 150V-350V | |
Threshold adjustment voltage | 2%-25% of Un selected | ||
Adjustment of asymmetry threshold | 5%-20% | ||
Hysteresis | 2% | ||
Phase failure value | 70% of Un selected | 70% of Un selected | |
Time delay | Adjustable 0.1s-10s,10% | ||
Measurement error | ≤2% | ||
Run up delayat power up | 0.5s time delay | ||
Konb setting accuracy | 10% of scale value | ||
Supply indication | green LED | ||
Output indication | red LED | ||
Reset time | 1s | ||
Output | 2×SPDT | ||
Current rating | 8A/AC1 | ||
Switching voltage | 250VAC/24VDC | ||
Min.breaking capacity DC | 500mW | ||
Temperature coefficient | 0.05%/℃,at=20℃(0.05%°F,at=68°F) | ||
Mechanical life | 1×10^7 | ||
Electrical life(AC1) | 1×10^5 | ||
Operating temperature | -20℃ to +55℃(-4F to 131F) | ||
Storage temperature | -35℃ to +75℃(-22F to 158F) | ||
Mounting/DIN rail | Din rail EN/IEC60715 | ||
Protection degree | IP40 for front panel/IP20 terminals | ||
Operating position | any | ||
Overvoltage category | III | ||
Pollution degree | 2 | ||
Max.cable size(mm²) | solid wire max.1×2.5or 2×1.5/withsleeve max.1×2.5(AWG 12) | ||
Tightening torque | 0.4Nm | ||
Dimensions | 90×18×64mm | ||
Weight | 68g-71g |