Automation Relay,Circuit Breaker,Contactor,Isolation Switch,Light,Other Electrical Equipment,Pneumatic,Power Quality,Solar Energy Storage System,Surge Protection Device,Timer Switch,Topsales Products,Transfer Switch,Ungrouped
Rated current In(A) | Adjusting rage of commuting current | The cutting capacity for rated limit short circuit Icu, the cutting capacity for rated work short circuit Ics | ||||||
230/240V | 400/415V | |||||||
Icu(kA) | Ics(kA) | Icu(kA) | Ics(kA) | |||||
0.16 | 0.10-0.16 | 100 | 100 | 100 | 100 | |||
0.25 | 0.16-0.25 | 100 | 100 | 100 | 100 | |||
0.4 | 0.25-0.4 | 100 | 100 | 100 | 100 | |||
0.63 | 0.4-0.63 | 100 | 100 | 100 | 100 | |||
1 | 0.63-1 | 100 | 100 | 100 | 100 | |||
1.6 | 1-1.6 | 100 | 100 | 100 | 100 | |||
2.5 | 1.6-2.5 | 100 | 100 | 100 | 100 | |||
4 | 2.5-4 | 100 | 100 | 100 | 100 | |||
6.3 | 4-6.3 | 100 | 100 | 100 | 100 | |||
10 | 6-10 | 100 | 100 | 100 | 100 | |||
14 | 9-14 | 100 | 100 | 15 | 7.5 | |||
18 | 13-18 | 100 | 100 | 15 | 7.5 | |||
23 | 17-23 | 50 | 50 | 15 | 6 | |||
25 | 20-25 | 50 | 50 | 15 | 6 | |||
32 | 24-32 | 50 | 50 | 10 | 5 |
Rated current In(A) | Adjusting rage of commuting current | The cutting capacity for rated limit short circuit Icu, the cutting capacity for rated work short circuit Ics | ||||||
440V | 500V | |||||||
Icu(kA) | Ics(kA) | Icu(kA) | Ics(kA) | |||||
0.16 | 0.10-0.16 | 100 | 100 | 100 | 100 | |||
0.25 | 0.16-0.25 | 100 | 100 | 100 | 100 | |||
0.4 | 0.25-0.4 | 100 | 100 | 100 | 100 | |||
0.63 | 0.4-0.63 | 100 | 100 | 100 | 100 | |||
1 | 0.63-1 | 100 | 100 | 100 | 100 | |||
1.6 | 1-1.6 | 100 | 100 | 100 | 100 | |||
2.5 | 1.6-2.5 | 100 | 100 | 100 | 100 | |||
4 | 2.5-4 | 100 | 100 | 100 | 100 | |||
6.3 | 4-6.3 | 50 | 50 | 50 | 50 | |||
10 | 6-10 | 15 | 15 | 10 | 10 | |||
14 | 9-14 | 8 | 4 | 6 | 4.5 | |||
18 | 13-18 | 8 | 4 | 6 | 4.5 | |||
23 | 17-23 | 6 | 3 | 4 | 3 | |||
25 | 20-25 | 6 | 3 | 4 | 3 | |||
32 | 24-32 | 6 | 3 | 4 | 3 |
Rated current In(A) | Adjusting rage of commuting current | The cutting capacity for rated limit short circuit Icu, the cutting capacity for rated work short circuit Ics | The distance of arcs(mm) | ||
690V | |||||
Icu(kA) | Ics(kA) | ||||
0.16 | 0.10-0.16 | 100 | 100 | 40 | |
0.25 | 0.16-0.25 | 100 | 100 | 40 | |
0.4 | 0.25-0.4 | 100 | 100 | 40 | |
0.63 | 0.4-0.63 | 100 | 100 | 40 | |
1 | 0.63-1 | 100 | 100 | 40 | |
1.6 | 1-1.6 | 100 | 100 | 40 | |
2.5 | 1.6-2.5 | 3 | 2.25 | 40 | |
4 | 2.5-4 | 3 | 2.25 | 40 | |
6.3 | 4-6.3 | 3 | 2.25 | 40 | |
10 | 6-10 | 3 | 2.25 | 40 | |
14 | 9-14 | 3 | 2.25 | 40 | |
18 | 13-18 | 3 | 2.25 | 40 | |
23 | 17-23 | 3 | 2.25 | 40 | |
25 | 20-25 | 3 | 2.25 | 40 | |
32 | 24-32 | 3 | 2.25 | 40 |